The sensor reaches the KNX bus through a bridge, because it speaks MQTT and HTTP over Wi-Fi. The bridge is a smart home hub with a KNX connection: it integrates the sensor and writes its values to group addresses. This is described for Home Assistant, ioBroker, openHAB and Node-RED. If one of them already runs on your bus, use that one. Fill level, contents, temperature and alarm are then available as group addresses for visualization and logic, in the direction sensor → KNX.
In the topics, <Hauptthema> stands for whatever is entered on the sensor under Connections → Main topic; replace it with your own value. The group addresses are examples.
Group addresses and datapoint types
In the ETS, create one group address for each value:
| Value | Source on the sensor | Group address (example) | Datapoint type |
|---|---|---|---|
| Fill level in % | stat/<Hauptthema>/REL_LEVEL |
5/0/1 |
DPT 5.001 (percent) |
| Contents in m³ | stat/<Hauptthema>/FILLING, divided by 1000 |
5/0/2 |
DPT 14.076 (volume) |
| Temperature in °C | temperature from tele/<Hauptthema>/STATE |
5/0/3 |
DPT 9.001 |
| MIN alarm | stat/<Hauptthema>/ALERT is MIN |
5/0/4 |
DPT 1.005 (alarm) |
| MAX alarm | stat/<Hauptthema>/ALERT is MAX |
5/0/5 |
DPT 1.005 (alarm) |
All topics and values of the sensor are listed in the user manual.
Bridge
First integrate the sensor following the instructions for your hub, then pass the values on to the group addresses using its KNX connection:
| Bridge | Integrate the sensor | Send to the bus |
|---|---|---|
| Home Assistant | Home Assistant: Integrating the level sensor | KNX integration, expose |
| ioBroker | ioBroker: Integrating the level sensor | KNX adapter |
| openHAB | openHAB: Integrating the level sensor | KNX binding |
| Node-RED | Node-RED: Integrating the level sensor | Appendix on that page, with ready-made function nodes |
Limitations
- The bridge is an additional device: if it or the broker goes down, the last value stays on the bus without KNX noticing.
- The values are sent on change, not cyclically. In the sensor's power saving mode they are as old as its last wake-up.
- DPT 5.001 only resolves percent in 255 steps (enough for a display).
- Only the direction sensor → KNX is described.
Verification status
Integrating the sensor into the hubs mentioned has been tested.