FHEM: Integrating the level sensor

Learn how to integrate the LiDAR level sensor LD and the radar level sensor RD into FHEM, with all settings on the sensor and on the hub.

Applies to LD and RD · Sensor firmware 4.2.8 and newer · As of 11/25/2026

Contents

FHEM integrates the sensor via MQTT. You connect FHEM to the broker the sensor is attached to (MQTT2_CLIENT), and define the sensor as a MQTT2_DEVICE using the block below. After that, fill level, contents, fill height, temperature and alarm are available as readings. Alarm limits and alarm switches can be set from FHEM.

<Hauptthema> stands in this guide for the value entered on the sensor under Main topic (e.g. zisterne). It must be entered in FHEM in exactly one place, see step 2.

Prerequisites

  • Sensor with firmware 4.2.8 or newer, on Wi-Fi, and with the settings under Tank Config completed
  • FHEM 6.x with the built-in modules MQTT2_CLIENT and MQTT2_DEVICE. No further Perl packages are required.
  • An MQTT broker on the network, e.g. Mosquitto.

Setting up the sensor

In the sensor's web interface, under Connections enter the connection type MQTT Broker, server and port of the broker, a unique Client id and a Main topic. Leave the switch Home Assistant switched off.

Setup

  1. Connect FHEM to the broker (skip if there is already an MQTT2_CLIENT for this broker). On the FHEM command line:

    define mqtt MQTT2_CLIENT <Adresse des Brokers>:1883
    

    Afterwards, the device mqtt must show opened. If the broker requires a login: attr mqtt username <Benutzer> and set mqtt password <Passwort>.

  2. Create the sensor. Open any device (e.g. mqtt), scroll to the very bottom and click Raw definition, replace the contents of the text field with the following block and click Execute commands. Beforehand, in the second line, replace zisterne with your main topic (only there). The device name Zisterne can be chosen freely, but then change it in all lines.

    define Zisterne MQTT2_DEVICE
    attr Zisterne devicetopic zisterne
    attr Zisterne readingList tele/$DEVICETOPIC/LWT:.* LWT\
    tele/$DEVICETOPIC/STATE:.* { json2nameValue($EVENT) }\
    stat/$DEVICETOPIC/[^/]+:.* { +{ lc(($TOPIC =~ m,([^/]+)$,)[0]) => ($EVENT eq "" ? "-" : $EVENT =~ m/^(True|False)$/ ? lc($EVENT) : $EVENT) } }
    attr Zisterne setList update:noArg cmnd/$DEVICETOPIC/UPDATE 1\
    mini:slider,0,1,100 cmnd/$DEVICETOPIC/MINI $EVTPART1\
    maxi:slider,0,1,100 cmnd/$DEVICETOPIC/MAXI $EVTPART1\
    alert_min:ON,OFF cmnd/$DEVICETOPIC/ALERT_MIN $EVTPART1\
    alert_max:ON,OFF cmnd/$DEVICETOPIC/ALERT_MAX $EVTPART1
    attr Zisterne stateFormat { ReadingsVal($name,"LWT","") eq "Online" ? ReadingsVal($name,"rel_level","-")." %" : "nicht erreichbar" }
    
  3. Save: at the top left Save config.

The readings fill immediately because the broker keeps the last value of each. The most important ones:

Reading Meaning
rel_level Fill level in %
filling Contents in liters
level Fill height in cm
temperature Temperature in °C
alert MIN, MAX or - (no alarm). Appears only once the sensor sends the topic for the first time
problem, out_of_range true / false
LWT Online / Offline

The values under stat/<Hauptthema>/… and the JSON from tele/<Hauptthema>/STATE end up in the same readings, written in lowercase.

Quick test

Execute on device Zisterne set … update: after a few seconds all readings carry the current time, and the status shows the fill level, e.g. 50 %. If the list stays empty, the main topic in the line devicetopic is wrong. Mind upper and lower case.

Optional

  • Setting values: set Zisterne mini 20 and set Zisterne maxi 85 set the alarm limits in %, set Zisterne alert_min OFF or alert_max ON switch the alarms. The sensor reports back the accepted value and discards an invalid one.

  • Report an alarm:

    define n_Zisterne_Alarm notify Zisterne:alert:.(MIN|MAX) { Log 1, "Füllstand-Alarm $NAME: $EVTPART1" }
    

    Instead of Log put your own notification method here (push, mail …).

  • Availability: The status shows nicht erreichbar (“not reachable”) as soon as the broker reports the sensor as Offline; the corresponding reading is called LWT.

  • Fewer events: attr Zisterne event-on-change-reading .* makes FHEM report a value only when it changes.

  • Chart: define FileLog_Zisterne FileLog ./log/Zisterne-%Y.log Zisterne:(rel_level|filling|level|temperature):.* logs the measured values. From this, you generate the chart with Create SVG plot on the FileLog.

  • FHEM itself as the broker (define mqttServer MQTT2_SERVER 1883 global, the sensor connects to FHEM): the same block works unchanged, but FHEM then also creates a device by itself with the sensor's Client id. You can delete it and switch it off with attr mqttServer autocreate no.

Limitations

  • There is no automatic setup: autocreate creates only a collective device for this sensor, with duplicate readings and no controls. The Tasmota templates (attrTemplate tasmota_…) do not fit despite the same topic names. Do not apply them.
  • If a measured value is missing, the reading shows - instead of a number. A chart then has a gap or an outlier at that point.
  • In power saving mode, LWT stays at Online, although the sensor is asleep, and set commands reach it only while it is awake.
  • The commands are sent without acknowledgment and without protection against loss (QoS 0). Whether a value arrived is shown by the reading of the same name.
  • If, for the MQTT2_CLIENT autocreate is switched on, you also get the sensor's topics in its collective device.

Verification status

Tested with FHEM 6.5 and sensor firmware 4.2.8.